Applications

  • Capturing fine particles
  • Second or final stage filter in HVAC
  • Pre-filter for HEPA filters

Highlights

  • Eurovent certified
  • High temperature resistant
  • Large filtration area
  • Simple and light weight
  • High dust holding capacity
  • Low initial pressure drop

Technical Specifications

Filter Standard:ISO 16890Max. Operating
Tempature:
120˚C
Filter Class:ISO ePM1 - ISO ePM2,5
- ISO ePM10
Faceguard:Available on request
Media:Glass FiberGasket:Available on request
Frame:PolycarbonateSealing Compound:Two component
polyurethane
Rec. Final Pressure Drop
EN13053:
Initial ΔP +100 Pa or
initial ΔP x3
whichever is lower
Seperators:Hotmelt

Order Code

Filter TypeFilter
Class
Dimensions (mm)FaceguardGasket
FVT : High
Temperature,
V-Compact Filter
M6
F7
F8
F9
592x592x292FW : Without
FC2: On 2 Edge Sides
FC8: On 8 Edge Sides
W: Without
P: Continuous Pu Foam
PP: Pu Foam on Both Sides
E: EPDM
EE: EPDM Flat On Both Sides
Filter ModelEN 779
(cancelled)
ISO 16890Filtration
Area
(m²)
Nominal
Airflow
(m³/h)
N. Initial
Pressure Drop
(Pa)
Rated
Airflow
(m³/h)
R. Initial
Pressure Drop
(Pa)
Energy
Class
FVT-M6-287-592-292-FW-WM6ePM10 75%92125100170070E
FVT-M6-490-592-292-FW-WM6ePM10 75%14,53500100270070E
FVT-M6-592-592-292-FW-WM6ePM10 75%184250100340070E
FVT-F7-287-592-292-FW-WF7ePM1 55%92125110170080D
FVT-F7-490-592-292-FW-WF7ePM1 55%14,53500110270080D
FVT-F7-592-592-292-FW-WF7ePM1 55%184250110340080D
FVT-F8-287-592-292-FW-WF8ePM1 60%92125130170090D
FVT-F8-490-592-292-FW-WF8ePM1 60%14,53500130270090D
FVT-F8-592-592-292-FW-WF8ePM1 60%184250130340090D
FVT-F9-287-592-292-FW-WF9ePM1 85%921251501700100D
FVT-F9-490-592-292-FW-WF9ePM1 85%14,535001502700100D
FVT-F9-592-592-292-FW-WF9ePM1 85%1842501503400100D

“Other dimensions are available on request.”
“Differential Pressure Tolerance ( ±10% + 5 Pa ) or ( 10 Pa + 5 Pa ) whichever is greater”