Applications

  • Residential HVAC filters
  • Commercial / Industrial HVAC filters

Highlights

  • Only mini-pleat media, no frame

Technical Specifications

Filter Standard:ISO 16890Rec. Final Pressure
Drop EN13053:
Initial ΔP +100 Pa or
initial ΔP x3
whichever is lower
Filter Class:ISO ePM1 - ISO ePM2,5
- ISO ePM10
Max. Operating
Tempature:
80˚C
Media:Glass fiberSeperators:Hotmelt

Order Code

Filter TypeFilter ClassDimensions (mm)
MP : Mini-Pleat
Media
M6
F7
F8
F9
584x1200x42
Filter ModelEN 1822ISO 16890Dimensions
WxHxD
(mm)
Filtration
Area
(m²)
Nominal
Airflow
(m³/h)
Initial
Pressure Drop
(Pa)
MP-M6-584-590-42M6ePM10 65%584x590x426.2200060
MP-M6-584-1200-42M6ePM10 65%584x1200x4212.4400060
MP-F7-584-590-42F7ePM1 55%584x590x426.2200080
MP-F7-584-1200-42F7ePM1 55%584x1200x4212.4400080
MP-F8-584-590-42F8ePM1 70%584x590x426.22000100
MP-F8-584-1200-42F8ePM1 70%584x1200x4212.44000100
MP-F9-584-590-42F9ePM1 85%584x590x426.22000145
MP-F9-584-1200-42F9ePM1 85%584x1200x4212.44000145
MP-M6-584-590-75M6ePM10 65%584x590x7512.4300070
MP-M6-584-1200-75M6ePM10 65%584x1200x7524.7600070
MP-F7-584-590-75F7ePM1 55%584x590x7512.4300090
MP-F7-584-1200-75F7ePM1 55%584x1200x7524.7600090
MP-F8-584-590-75F8ePM1 70%584x590x7512.43000110
MP-F8-584-1200-75F8ePM1 70%584x1200x7524.76000110
MP-F9-584-590-75F9ePM1 85%584x590x7512.43000145
MP-F9-584-1200-75F9ePM1 85%584x1200x7524.76000145

“Other dimensions are available on request.”
“Differential Pressure Tolerance ( ±10% + 5 Pa ) or ( 10 Pa + 5 Pa ) whichever is greater”